- 额定功率
- 电流/电压
- 外壳材质
- 充电方式
- 功能支持
- 安装方式
Cost-effective
Save money and delivering high quality without excessive expense.
plug-and-play
No setup required; simply connect and start using immediately.
Highy integrated
Combines diverse functions into a single, compact unit, eliminating the need for multiple separate devices.
Easy installation and maintenance
Features a straightforward setup and simple upkeep, with minimal tools or expertise required.
Model | HF-P 250kW-1200kWh | HF-P 500kW-1200kWh |
AC data | ||
Rated power (kW) | 250 | 500 |
Rated voltage (V) | 400 | |
Voltage range (V) | 320-460 | |
Rated current (A) | 361 | 722 |
Rated frequency (Hz) | 50/60 | |
Frequency range (Hz) | 45-55 / 55-65 | |
THDi (on-grid) | <3% | |
THDu (off-grid) | ≤1% linear; ≤5% non-linear | |
Power factor | 1 leading~1 lagging (settable) | |
Overload capacity | 110% long-term | |
AC output | 3W+N+PE | |
Isolation transformer | Integrated | |
On / off-grid switching | Support | |
PV data | ||
Max. PV input voltage (V) | 330/412.5 | 600/742.5/825 |
MPPT module quantity | 4月5日 | 2008/9/10 |
MPPT operating voltage range (V) | 250-1000 | |
Buck-boost mode | Support | |
Battery data | ||
Cell type | 3.2V/314Ah/LFP | |
Nominal voltage (V) | 768V/1P240S | |
Nominal energy (kWh) | 1205.76 | |
Working voltage range (V) | 672~850 | |
Max. charge and discharge rate | 0.5C@25℃ | |
Number of battery cycles | ≥6,000 | |
System data | ||
System specification | 500kW/1205.76kWh | |
Dimensions W×D×H (mm) | 6,058×2,438×2,896 | |
Net weight (kg) | 26000 | |
Operating temperature (℃) | 0 ~ +45 | |
Relative humidity | 0~95% (non-condensing) | |
Ingress protection | IP54 | |
Noise emission (dB) | <75 | |
Max. operating altitude (m) | 5,000 (>3,000 derating) | |
Cooling | Intelligent air cooling | |
Fire extinguishing system | Compartment-level total flooding gas fire suppression (FM200/Aerosol) | |
EMS communication | RS485, TCP/IP | |